Output Power:
3000W
Output Type:
Single
Input Voltage:
220V
Output Voltage:
48V
Output Frequency:
50/60Hz
Output Current:
50A
Efficiency:
96%
Application:
for Telecom Equipment,Battery Charging
use in:
exchange room, server room,base station,data communication
size after package:
62*52*180(cm)
weight:
18kg after carton package
with:
1pcs 50A rectifier module,1pcs monitor ,2 pcs fake module
Input:
single phase 220v or 3phase 380v
AC-DC Rectifier System:
Supply DC Power for DC Load and Charging for Battey
cell / whatsapp:
0086-13609617211
Skype:
fay6134688
SupplyAbility
SupplyAbility:
200 Piece/Pieces per Week
Packaging & Delivery
Packaging Details
carton or wooden cases
Port
shenzhen
Lead Time :
two days
 

 

Product Description

Power supply modules of series SET- 24V/48V/220V/110V are compact battery charging rectifiers 

with rear side connectivity. 

The rectifiers are designed for high voltage Power Plants and Substations.

 

Due to the modular concept and a high scalability the user is able to equip the power supply with 

additional modules according to his actual power profile. The chargers are very user friendly and

can be swapped as well as upgraded during system operation.

 

The devices get their operation parameters via the system RS 485 communication bus. 

After a successful login a central monitoring unit controls and monitors the devices. In case of interruption

due to failure of monitoring unit the modules operate continuously with internal default values.

Therefore the supply of the connected loads and the charging of the batteries are guaranteed without any 

interruption. 

Step less temperature control fan speed & change with the output power of module, which minimize 

noise & extend fan life.The rectifier needs a 1Ph AC mains connection.

 

Rectifier power circuit is divided into active PFC & DC to DC converter which can make the wide

input voltage range (85V-290V) & high efficiency.High power density has reached the international

advanced level.

 SPECIFICATION 

Input

 

Type

48V/50A

24V/70A

220V/10A

110V/20A

Model No.

 SET-48V/50A               

SET-24V/70A    

SET-220V/10A

 SET-110V/20

Input voltage

75-300VAC (Nominal 175-300VAC)

Input current

11.5A

10A

13.6A

Input frequency range

45 Hz-65 Hz

Power Factor

≥ 0.99 at P nom ≥ 75%

 

Output 

Nominal output voltage (Vnom)

48VDC

24VDC

220VDC

110VDC

Adjustable output voltage range

42-59Vdc

21V-28Vdc

190-300VDC

95-150VDC

Voltage Stabilization Accuracy

                           ± 0.5%

Current Stabilization Accuracy

                          ± 1 %

Nominal output current (Inom)

50ADC@50V

70ADC@24V

10ADC@300VDC

20ADC@150VDC

Efficiency

≥ 96 %

Charge characteristic line

IU Characteristic according to
DIN41772/DIN41773

Default value of the charging
voltage

50V

24V

240V

120V

O/p Overvoltage Vo> (factory
set)

60V

29V

302V

151V

Voltage ripple

≤ 200 mV

Dynamic accuracy of the
charging voltage

<3% of Venom at load change
from 10% -90%-10% ;Transient
time <50 ms

Short circuit protection

15% - 30% of Inom when in short
circuit

Parallel operation

Yes .Current Sharing ± 3%

 Mechanical: 

Type

48V/50A

24V/70A

220V/10A

110V/20A

Model No.

 SET-48V/50A               

SET-24V/70A    

SET-220V/10A

 SET-110V/20

Weight approx.

2.6KG

2KG

Dimensions (W/H/D)

103x88x261

Type of enclosure /
Protection class

IP 20

Color (front panel)

Front Black

 

Communications interface

RS 485

Ambient temperature

Operation: -20° to+55° C ,                     

 Storage:-40° to +70° C

Humidity

≤ 90 % RH

Cooling

Fan Cooled

Climatic conditions

IEC-68-2-2, IEC-68-2-3, IEC-68-2-6

Max. Installation altitude

≤2000 m

Audible noise

< 50 db

Connections

AC Input DC Output and Signalization at rear

CE conformity

Yes

Compliance to EMC standards

EN61000-4-2, EN-61000-4-6,                           EN-61000-4-3, EN-61000-4-12

Air Pressure

70-106 Pa

Insulation Resistance

Input Chassis & Output > 10M Ohms at 500VDC

Dielectric strength

2000V between Input, Output & Chassis for 1Min.